October 9, 2026

Motor Nameplate Reading: Full Guide to Understanding 3-Phase Motor Data

A technician sets the thermal overload relay to 21A on a motor wired for 320V. The motor runs fine at light load but trips repeatedly under normal conditions. The nameplate showed 42/21A: 42A is the FLA at 230V, and 21A is the correct value for 460V operation. The overload was set to half the right number.

Dual-voltage confusion is the most common nameplate misread, but insulation class in high-ambient locations, service factor in VFD applications, and the code letter when sizing breakers each have their own failure modes. Every field on the nameplate is covered below, with worked examples for 15 HP and 25 HP motors.

Table of Contents

  1. Power Rating: HP vs. kW
  2. Voltage and Dual-Voltage Motors
  3. Full Load Amperes (FLA)
  4. Speed, Frequency, and Slip
  5. NEMA Frame Designation
  6. Insulation Class
  7. Service Factor
  8. Design Letter, Enclosure, and Code Letter
  9. 15 HP Motor Nameplate: Worked Example
  10. 25 HP Motor Nameplate: Worked Example
  11. Lenze Motor Nameplate: IEC Format
  12. Common Mistakes

Power Rating: HP vs. kW

The nameplate HP is the motor's rated mechanical output at the shaft, not input power. Because no motor is 100% efficient, electrical input is always higher.

For a 15 HP motor at 91% efficiency:

Pinput=15×0.7460.91=11.190.91=12.3 kWP_{input} = \frac{15 \times 0.746}{0.91} = \frac{11.19}{0.91} = 12.3 \text{ kW}

NEMA motors are rated in horsepower; IEC motors (including Lenze) use kilowatts. The conversion is 1 HP = 0.746 kW, so 11 kW is approximately 15 HP.

Standard NEMA sizes follow a fixed sequence: 1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 40, 50 HP. If your calculated load falls between sizes, select the next one up.

Voltage and Dual-Voltage Motors

A rating of 230/460V does not mean the motor accepts any voltage in that range. It means two distinct winding configurations:

  • 460V wye connection: 21A FLA for a 15 HP motor
  • 230V delta connection: 42A FLA for the same motor

Both configurations deliver the same 15 HP at the shaft. The connection is made in the terminal box using T-lead jumpers.

  • 460 V (high-voltage connection): T4-T7, T5-T8, and T6-T9 are tied together in pairs; line conductors connect to T1, T2, and T3.
  • 230 V (low-voltage connection): T4, T5, and T6 are tied together; line conductors connect to T1-T7, T2-T8, and T3-T9.

warning

On a 460V system, always use the 21A value for overload relay settings and cable sizing, not 42A. The 42A figure applies only at 230V.

Full Load Amperes (FLA)

FLA is the current drawn at rated voltage when producing rated HP. Three decisions hinge on it:

  • Overload relay setting: 100-115% of FLA (up to 125% if SF (Service Factor) is 1.15 or higher, per NEC 430.32)
  • Branch circuit conductor: minimum 125% of FLA (NEC 430.22)
  • VFD output current rating: must meet or exceed motor FLA

FLA can be calculated from nameplate data:

I=HP×7463×V×η×PFI = \frac{HP \times 746}{\sqrt{3} \times V \times \eta \times PF}

For a 15 HP, 460V motor with efficiency of 91% and power factor of 0.88:

I=15×7461.732×460×0.91×0.88=11,190643.5=17.4 AI = \frac{15 \times 746}{1.732 \times 460 \times 0.91 \times 0.88} = \frac{11,190}{643.5} = 17.4 \text{ A}

The nameplate shows 21A, slightly higher because NEC Table 430.250 values include a margin. Use nameplate FLA for protection settings, not the calculated value.

Speed, Frequency, and Slip

Nameplate RPM is the full-load speed, always less than synchronous speed. For a 4-pole, 60 Hz motor:

Ns=120×604=1800 RPM (synchronous)N_s = \frac{120 \times 60}{4} = 1800 \text{ RPM (synchronous)}

A nameplate speed of 1760 RPM gives a full-load slip of:

s=1800−17601800=2.2%s = \frac{1800 - 1760}{1800} = 2.2\%

Slip increases with load. A heavily loaded induction motor runs measurably slower than nameplate speed. Induction motors are not constant-speed machines: if speed accuracy matters for the application, a VFD with closed-loop encoder feedback is needed.

NEMA Frame Designation

The frame number encodes the motor's physical dimensions. For frame 215T:

  • Shaft height (D): 215 / 16 = 13.44 inches from base to shaft centerline
  • "T" suffix: NEMA T-frame standard (post-1964), which standardized shaft diameter, keyway, and bolt pattern across manufacturers

A 215T from any NEMA-compliant manufacturer is mechanically interchangeable with a 215T from any other.

HPTypical FrameShaft Height
15215T13.44"
20256T16.00"
25284T17.75"
30286T17.75"

Insulation Class

Insulation class sets the maximum permissible winding temperature:

ClassMax Winding TempRise at 40°C Ambient
B130°C80°C
F155°C105°C
H180°C125°C

Class F is standard on most new motors. Running a Class F motor at Class B temperature rise (80°C instead of 105°C) roughly doubles insulation life. Some manufacturers label this "F/B" on the nameplate and market it as an extended-life feature.

Above 40°C ambient, the permissible rise decreases. A Class F motor in a 50°C enclosure has 95°C of rise budget instead of 105°C, which reduces its continuous load capacity. At 55°C ambient, that margin narrows to 90°C of rise before the winding hits its thermal limit.

Service Factor

SF is the permitted overload multiplier under nameplate conditions: rated voltage, rated frequency, and 40°C ambient. SF 1.15 on a 15 HP motor means 17.25 HP is permissible continuously under those conditions.

Running in the service factor zone increases winding temperature significantly. For every 10°C rise above Class B levels, insulation life roughly halves. A motor running at its SF ceiling continuously will have a shorter service life than one operating at 100% rated load.

For VFD applications: treat SF as 1.0. Harmonic currents and voltage spikes from the drive add winding stress beyond what the nameplate SF accounts for.

Design Letter, Enclosure, and Code Letter

NEMA Design Letter

DesignStarting TorqueLocked Rotor CurrentTypical Application
BNormal6-7x FLAPumps, fans, general purpose
CHigh6-7x FLAConveyors, loaded compressors
DVery high6-7x FLAPunch presses, cranes, hoists

Design B covers most industrial applications. If no design letter appears on the nameplate, it is Design B.

Enclosure Types

CodeNameUse Case
ODPOpen Drip-ProofIndoor, clean, horizontal mounting
TEFCTotally Enclosed Fan CooledOutdoor, dusty, wet environments
TENVTotally Enclosed Non-VentilatedSmall motors, clean environments
XPExplosion-ProofClass I, II, III hazardous locations

Code Letter

The code letter defines locked rotor kVA per horsepower. For Code G (5.6 to 6.3 kVA/HP), a 15 HP motor:

LR (Locked Rotor) kVA=15×6.0=90 kVA\text{LR (Locked Rotor) kVA} = 15 \times 6.0 = 90 \text{ kVA} ILRC=90,0003×460=113 A≈5.4×FLAI_{LRC} = \frac{90{,}000}{\sqrt{3} \times 460} = 113 \text{ A} \approx 5.4 \times \text{FLA}

This locked rotor current feeds into breaker sizing per NEC Table 430.52 and determines the transformer inrush load when the motor starts.

15 HP Motor Nameplate: Worked Example

15 HP 3-phase TEFC motor nameplate showing voltage, FLA, frame designation, and insulation class

Figure: Typical nameplate for a 15 HP, 460V, TEFC induction motor.

ParameterValueWhat It Means
HP15Rated shaft output (11.2 kW)
Volts230/460Delta at 230V, wye at 460V
Amps42/21FLA: 42A at 230V, 21A at 460V
RPM1760Full-load speed, 4-pole
Hz60Supply frequency
Phase3Three-phase
Frame215T13.44" shaft height
Ins. ClassFMax 155°C winding temp
S.F.1.1517.25 HP permissible under nameplate conditions
DutyCont.Continuous
DesignBStandard torque and starting current
Encl.TEFCOutdoor-rated enclosure
Amb.40°CStandard ambient
CodeGLRC: 5.6-6.3 kVA/HP
PF0.88Full-load power factor
Eff.91.0%NEMA Premium efficiency

Field engineering decisions from this nameplate:

  1. Overload relay: 21A x 1.15 = 24.2A (NEC 430.32 permits 125% of FLA when SF is 1.15 or higher)
  2. Branch circuit conductor: 21A x 1.25 = 26.3A minimum, select #10 AWG at 75°C (30A rated)
  3. Starting current: 113A locked rotor, verify transformer capacity can handle the inrush without pulling voltage below 85% on adjacent loads

25 HP Motor Nameplate: Worked Example

ParameterValueWhat It Means
HP25Rated shaft output (18.6 kW)
Volts230/460Delta at 230V, wye at 460V
Amps68/34FLA: 68A at 230V, 34A at 460V
RPM1760Full-load speed, 4-pole
Frame284T17.75" shaft height
Ins. ClassFMax 155°C winding temp
S.F.1.1528.75 HP permissible
CodeGLRC: 5.6-6.3 kVA/HP
PF0.87Full-load power factor
Eff.93.0%NEMA Premium efficiency

At 460V, the 25 HP motor draws 34A: 62% more current for 67% more output power. The close correspondence between those two percentages reflects the efficiency gain from 91% to 93% at the larger frame size. Larger motors are generally more efficient, and the 25 HP tier benefits from lower I²R losses relative to output.

Starting current (Code G):

LR kVA=25×6.0=150 kVA\text{LR kVA} = 25 \times 6.0 = 150 \text{ kVA} ILRC=150,0001.732×460=188 A≈5.5×FLAI_{LRC} = \frac{150{,}000}{1.732 \times 460} = 188 \text{ A} \approx 5.5 \times \text{FLA}

Branch circuit conductor: 34A x 1.25 = 42.5A, select #8 AWG at 75°C (50A rated).

For reference, overload relay setting: 34A x 1.15 = 39.1A (SF 1.15, same NEC 430.32 logic as the 15 HP).

Lenze Motor Nameplate: IEC Format

Lenze motors turn up frequently on imported conveyors, packaging lines, and servo systems. The IEC nameplate differs from NEMA in several fields that matter for replacement and protection.

ParameterNEMA (North America)IEC/Lenze (Europe)
PowerHorsepower (HP)Kilowatts (kW)
Frame size215T, 284T (inches)IEC 160M, 160L (mm)
Voltage (60 Hz)460V460 delta
Voltage (50 Hz)—400 delta / 690 wye
Efficiency classNEMA PremiumIE2, IE3, IE4
Power factor labelPFcos phi
Duty cycleCont.S1
Insulation classF, HSame letters, same limits

An 11 kW Lenze motor is the IEC equivalent of a 15 HP NEMA motor (11 / 0.746 = 14.75 HP). The dual voltage rating 400 delta/690 wye means delta connection at 400V for standard European distribution, or wye at 690V for high-voltage industrial supplies.

When replacing a Lenze motor with a NEMA motor, shaft output and speed can be matched, but mounting dimensions cannot. IEC 160M and NEMA 215T are not bolt-compatible: an adapter plate is required.

info

When programming a VFD for a Lenze motor on a 60 Hz North American system, confirm the base frequency listed on the nameplate. A 50 Hz IEC motor running on a 60 Hz VFD without frequency adjustment will run 20% faster than its rated speed, exceeding the mechanical design limit.

Common Mistakes When Reading Motor Nameplates

Using the wrong FLA for a dual-voltage motor

On a 460V system, the overload relay gets set to 21A, not 42A. Set it to 42A and the motor can run 100% overloaded before protection activates. Both values appear on the nameplate; the smaller one applies at the higher voltage.

Ignoring insulation class in high-ambient locations

A Class F motor in a 55°C enclosure has 100°C of temperature rise budget, not 105°C. That 5°C reduction sounds minor but it is the difference between a motor with adequate thermal margin and one that runs right at its limit under full load. Class H is the correct choice for sustained elevated ambient conditions.

Overlooking the code letter

The code letter determines locked rotor kVA, which feeds directly into NEC Table 430.52 for breaker selection and into transformer inrush calculations at startup. Skipping it leads to nuisance tripping on motor start or undersized protection that passes inspection but fails in service.

Assuming IEC and NEMA frames are physically interchangeable

Same kilowatt rating, same shaft speed, different bolt pattern and dimensions. An IEC 160M motor does not drop into a NEMA 215T mounting without an adapter plate. Check frame compatibility before ordering any replacement, especially on older European-origin machinery.



Calculators


Credits

⭐ Was this article helpful?

IDAR Mohamed

IDAR Mohamed

Electrical Engineer

Electrical Engineer specialized in power systems, electrical installations, and energy efficiency. Passionate about simplifying complex electrical concepts into practical guides. (University of applied sciences graduate, with experience in HV/LV systems and industrial installations.)

  • Motors and Drives
  • Motor Control
  • Electrical Testing and Calibration
Share it: